This all new Server Technology 3-Phase 208V Basic PDU features RamLock, a self-locking, elbow-catch mechanism to prevent accidental cord disconnects on standard network power cords along with HDOT Cx, a hybrid C13/C19 outlet that accepts either an IEC C14 or C20 plug. The PDU features 18 dedicated HDOT C13 outlets and 18 HDOT Cx which can be treated as either a C13 or C19 outlet. Select either 20A or 30A input current and 3-phase Delta or 3-phase Wye input phase for a power capacity of 5.7kW – 8.6kW for all your server rack power needs.
| ELECTRICAL | |
| Voltage | 208V 3-Phase Delta or 3-Phase Wye |
| Input Current (A) | 20 or 30 amp |
| Outlets | 18 x RamLock C13 + 18 x RamLock Combo C13/C19 (cX) |
| Circuit Protection | 2-pole, 20A trip circuit breakers, three (3) branch, rating: ≤ 16A, 10 kAIC Interrupt Rating |
| Inlet | NEMA L21-30P, or NEMA L15-20P |
| PHYSICAL | |
| Product | 2.2W x 2.5D x 70 H (inch) |
| Net Weight | 30 (lbs) |
| ENVIRONMENTAL | |
| Operating Temperature | 0 to 60° (32 to 140°) |
| Storage Temperature | -30 to 80° (-22 to 176°) |
| Operating Humidity | 8 to 90%, non-condensing |
| COMPLIANCE | |
| Safety Certificates | Safety (Listed & Certified, cTUVus mark) UL 62368-1 CSA C22.2 No. 62368-1 |
| MPN | Input Current | Input Current Rated (de-rated) | Input Phase | Input Plug | Input Power Capacity |
| C3B36RL-YCJE0AT3 | 30A | 24A | 3-Phase Wye (L-L) | NEMA L21-30P | 8.6 kW |
| C3B36RL-DCJE0AT | 30A | 24A | 3-Phase Delta (L-L) |
NEMA L15-30P | 8.6 kW |
| C3B36RL-DBJE0AT | 20A | 16A | 3-Phase Delta (L-L) |
NEMA L15-20P | 5.8 kW |
No resources are available for this product at this time.
Request a document below.*
For information regarding orders or shipping, please visit the Ordering Information page.
*Subject to availability