InfraPower 208V C13 Slide Lock (L13) Outlet Monitored PDU:
Current: 20A or 30A
Voltage: 208V Single-Phase
Input Plug: L6-20P for 20A and L6-30P for 30A
Input Cord: 10ft UL SJT 10 AWG cordset
Outlets: C13 Slide-locking Outlets
Circuit Breakers: (1 or 2) Hydraulic MCB
Mounting: 0U Vertical
The InfraPower Zi Series C13 Slide Lock Outlet Monitored PDU is single-phase PDU designed for cost efficient, reliable power distribution for your rack. Includes Embedded Dual IP, Strip and Circuit Monitoring. Now with the innovative slide-locking outlets.
InfraPower Outlet Monitored 208V L13 PDU Specifications:
| ELECTRICAL | |
| Voltage | 208V Single-Phase |
| Rated Amperage | 20 or 30 amp |
| Outlets | Locking C13 (L13) |
| Circuit Protection | 1 or 2 Hydraulic MCBs Single Circuit (20A): 16Amax Circuit A & B (30A) : 12Amax |
| Inlet | NEMA L6-20P or L6-30P 10ft cordset 3W 10 or 12 AWG UL SJT |
| METER FEATURES | |
| Local Display | Field replaceable 2.8" color LCD with touchscreen |
| Bank Measurement | Current (A), Energy (kWh), Voltage (V) & Power factor |
| Outlet Measurement | Current (A), Energy (kWh) |
| Accuracy | +/- 0.5% Billing-grade |
| IP Connection | Embedded dual Gigabit Ethernet LAN IP |
| Cascade | Up to 32 PDUs under one IP address |
| USB-C Function Port x 1 | Supports Wi-Fi, Firmware updates, Backup power for meter |
| Sensor Port x 1 | Supports single or daisy chain sensors (up to 4) |
| PHYSICAL | |
| Product | 2.2W x 2.7D x 41.3 - 51.2 H (inch) |
| Package | 4.3W x 10.6D x 54.8 - 70.1 H (inch) |
| Gross Weight | 15 (lbs) |
| Net Weight | 12.7 (lbs) |
| ENVIRONMENTAL | |
| Operating Temperature | -5 to 60° (23 to 140°) |
| Storage Temperature | -25 to 65° (-25 to 149°) |
| Operating Humidity | 8 to 95%, non-condensing |
| Operational Altitude | 0 to 2,000 m |
| Storage Altitude | 0 to 15,000 m |
| COMPLIANCE | |
| EMC Certificates | FCC : FCC 47 CFR Part 15 Subpart B, ICES-003 Issue 7 |
| Safety Certificates | CB : IEC 62368-1:2014 UL-US : UL 62368-1, 2nd Ed. UL-CA : CSAC22.2 No. 62368-1-14, 2nd Ed. |
| Environment | RoHS, Reach & WEEE |
| MPN | Amps | Outlets | Input Plug | Circuit Protection |
| V8L13-30A-Zi/CR_L630/3B-1 | 20 | 8 x L13 | L6-20P | 1 x MCB 16A max |
| V8L13-20A-Zi/CR_L620/3B-1 | 30 | 8 x L13 | L6-30P | 2 x MCB 12A max per Circuit |
| V12L13-20A-Zi/CR_L620/3B-1 | 20 | 12 x L13 | L6-20P | 1 x MCB 16A max |
| V12L13-30A-Zi/CR_L630/3B-1 | 30 | 12 x L13 | L6-30P | 2 x MCB 12A max per Circuit |
| V16L13-20A-Zi/CR_L620/3B-1 | 20 | 16 x L13 | L6-20P | 1 x MCB 16A max |
| V16L13-30A-Zi/CR_L630/3B-1 | 30 | 16 x L13 | L6-30P | 2 x MCB 12A max per Circuit |
| V20L13-20A-Zi/CR_L620/3B-1 | 20 | 20 x L13 | L6-20P | 1 x MCB 16A max |
| V20L13-30A-Zi/CR_L630/3B-1 | 30 | 20 x L13 | L6-30P | 2 x MCB 12A max per Circuit |
| V24L13-20A-Zi/CR_L620/3B-1 | 20 | 24 x L13 | L6-20P | 1 x MCB 16A max |
| V24L13-30A-Zi/CR_L630/3B-1 | 30 | 24 x L13 | L6-30P | 2 x MCB 12A max per Circuit |