12 Volt - 140 Amp Hour - FR - Elite UPS Replacement Battery

All batteries are not created equal. Gruber manufactured the 58EGPS-12-140-I specifically for electronic equipment and offers one of the longest shelf lives assuring your equipment long life and reliability.

Gruber 58EGPS-12-140-I:
  • Voltage: 12V
  • Amp/H: 140AH
  • Terminal: T8
Gruber 58EGPS-12-140-I - Click to enlarge



Price
$353.90
Please call 1-866-722-5776 to order

Features:

  • 4 Year Warranty on UPS applications with climate control, and a constant float trickle charge connected to a UPS.
  • 1 Year Warranty on Golf Carts, Wheelchairs, Mall Carts, Hotwheels Kids Toys, or where batteries are continuously deep discharged between charges.
  • Lead alloy with low calcium minimizes gassing and extends the life of the grid.
  • Through unique active material recipes, plates after undergoing curing and tank formation provide outstanding energy density and ensure the quality of the battery.
  • Using brass coated lead alloy battery terminals minimizes the impedance of connecting cells inside.
  • Fire Retardant case made of ABS resin and cells kept under internal pressure protects from outer shock or impact.
  • Micro-porous AGM separator completely absorbs and retains electrolyte under the pressured cell design.
  • Electrolyte sufficiently serves for electrochemical reactions in battery but never spills.
  • Battery cases are sealed in epoxy and cells are covered with vents to avoid cell contamination with the atmosphere and serve for internal oxygen reaction.
  • With very little gas evolution, the water loss is minimized and service life is extended. Excess pressure and gas will be released which ensures safety.
  • Vent design is certificated by UL.
Battery Type12Volt, 140 Amp Hour
Capacity
490.9 Watts/cell15min rate (1.67V/cell)
140 AH20HR (1.80V/cell)
Dimensions
Length335mm (13.19in)
Width172mm (6.77in)
Height275mm (10.83in)
Total Height278mm (10.94in)
Approx Weight92.6Lbs.(42kg)
Self Discharge<3% of capacity declined per month at 25°C
CurrentMax. Discharge Currents(5s): 1848A
Initial Charging Current: <42.6A
Operating Temp Range
Charge0°c(32°f) to 40°c (104°f)
Discharge-15°c(5°f) to 50°c (122°f)
Storage-15°c(5°f) to 40°c (104°f)
Internal ResistanceApprox. 3.2 mΩ
Container MaterialABS
TerminalT8