Server Room Monitoring: RLE RLE F1000-M

Server Room Monitoring: RLE RLE F1000
Server Room Monitoring: RLE RLE F1000
Alarm Monitoring & Notification System w/ Modem
 

Please note, the RLE F1000-M is discontinued. For alternative options, please see Rack / Room Monitoring. For additional upgrade options, contact your Server Racks Online sales representative at 1-866-722-5776.

RLE's Falcon F1000-M w/ modem, is a monitoring and notification system for small and medium size system needs. This stand alone, integration-friendly systems provide equipment protection by monitoring critical operating and environmental parameters in communication rooms, unmanned facilities, critical support systems, and enterprises worldwide.

The Falcon F1000-M is ideal for monitoring analog (4-20mA), digital dry contact, or thermistor signals from devices such as temperature and humidity sensors, gas and smoke detectors, fire suppression systems, surveillance products, leak detection systems, power monitoring systems, uninterruptible power supplies, PDUs, generators, DC power plants, commercial power, HVAC units, ATSs and TVSSs.

The Falcon F1000-M operates via embedded firmware that handles all data collection, alarm reporting, and multiple concurrent communication mediums. The embedded firmware enables system configuration, I/O setup, status inquiries, alarm reports, data logs, and troubleshooting without purchase of additional software. Both systems can be accessed, viewed and configured with any Web browser or through direct-connect application software such as HyperTerminal.

Redundant alarm notification is possible with the F1000-M via email, SNMP, Modbus slave RTU or TCP/IP, and paging via modem. This system can send email to up to four recipients. Also, with an internal PPP-enabled modem, direct dial out to up to four phone numbers is possible. RLE's Falcon F1000-M can accommodate up to four analog, four digital dry contact or thermistor signals, as well as two relay outputs.

Server Room Monitoring: RLE RLE F1000-M - Click to enlarge



RLE Falcon F1000-M Features & Benefits:

  • Versatile alarm monitoring
  • Allows multiple inputs
  • Convenient viewing of alarms
  • Modbus plug-and-play with most of RLE’s leak detection products
  • Modbus, BACnet, and SNMP output
  • Monitors up to 16 servers or other IP devices
  • Displays images from up to five IP cameras
  • Multi-protocol and redundant alarm notification
  • Monitors digital, analog, or thermistor input signals
  • F1000-M - 8 inputs
  • Web browser accessible; no proprietary software required
  • Easily integrates with RLE’s Modbusenabled leak detection equipment
  • Simple integration to building management system (BMS)
  • Manageable for network management system (NMS)
  • Consolidates systems into one, easy-touse monitoring solution
  • Enhances security for authorized areas
  • Quickly informs key personnel of pending problems

RLE Falcon F1000-M Specifications:

Physical Characteristics

 
Width 16.8 in. (427mm.)
Height 1.8 in. (46mm.)
Depth 7.9 in. (201mm.)
Weight 6 lbs. (2.72kg)
Power 4 Configurable as 4-20mA (12-bit A/D conversion), 4 as Digital Input or Thermistor
Environment  
Storage Temperature -40°F to 185°F (-40°C to 85°C)
Operating Temperature 32° to 158°F (0° to 70°C)
Humidity Humidity: 5% to 95% RH, non-condensing
Altitude 15,000ft (4,572m) max
Inputs- Analog/Digital 4 Configurable as 4-20mA (12-bit A/D conversion), 4 as Digital Input or Thermistor and 24 Digital Input (<15mA)
Outputs- Relay 2 Dry Contact, Form C, 1A @ 24VDC, 0.5A resistive @ 120VAC
Communication Ports  
Ethernet 10 BaseT, RJ45 connector; 500VAC RMS isolation
RS-232

DB9 female connector; 9600 baud; 3000VAC RMS optically isolated; 15kV ESD protection

RS-485 (selectable as RS-232) Two-wire half duplex; terminal block (selecting RS-232 switches to DB9 male connector); 9600 baud; 3000VAC RMS optically
isolated
Modem (RJ11 Telco) - V.34bis/33.6 kbps; PPP-Enabled; FCC Part 68 approved; 1500VAC RMS isolation barrier; 2100V peak surge protection;
Protocols  
TCP/IP; UDP/IP; ICMP/IP; FTP; NTP;
Telnet; HTTP/HTML
IPv4.0; up to 5 URL links to other IP addressable cameras/devices; webpages comply with Rehabilitation Act of 1973, sections
504 and 508, US Dept of Education (web site accessibility for computer users with disabilities)
SNMP V1; MIB-2 compliant; NMS Manageable with Get, Set, and Traps; V2c- Traps or Informs
SMTP (email) Supports Client Authentication (plain and login); compatible with ESMTP Servers
Modbus

RTU transmission protocol; function codes: Slave - 03; Master - 03, 04 (RLE leak detection equipment only)

Modbus/IP Modbus Slave; TCP/IP transmission protocol
BACNet/IP Conformance Level 1
Terminal Emulation VT100 compatible
TAP (Pager) Telocator Alphanumeric Protocol Ver1.8
Alarm Notification  
Pager (Modem)

4 Text, numeric and/or alphanumeric pager numbers; each Digital and Analog Alarm (HighLimit2 and LowLimit2) can notify any
4 of the 4 pagers;
Email (Ethernet, Modem PPP) 4 Email recipients; email sent on Alarm and Return To Normal; each Alarm can notify any or all of the 4 email recipients;
SNMP Traps (Ethernet) 8 Community Strings
Escalation Additional notification to 1 of the 4 pager numbers when initial page results in Failure To Acknowledge status
Internal Hardware  
Real Time Clock Battery backed; ±1.53 min/month accuracy
Memory

512K RAM; 128K NVRAM; 64K ROM; 2M Flash
Logging Capabilities  
Alarm Log

Last 100 Alarms

Event Log Last 100 Events (e.g., Acknowledgement By Code, System Boot, Page Successful, etc.)
Web User Access Log Last 100 HTML Accesses (User, Date, and Time)
Digital Status Log Last 100 Digital Status entries
Trending of Analog Inputs 244 entries per time frame, per channel. High, low, and average values logged over specific minutes, hours, and days.
Login Security  
Web Browser Access (Ethernet,
Modem PPP)
1 Administrator plus 7 Users individually selectable for Read Only, Read/Write or Administrator;
Terminal Emulation Access 1 Administrator (password for both Modem and RS-232) plus 1 Read Only (password for Modem only, not RS-232)
Web Browser Access 1 Universal web password for administrator access
Front Panel Interface 1 on/off power switch. Red and green LEDs indicate status, network link, network activity, and modem activity
Mounting Rack mount, or wall mount (brackets required): WMB wall mount brackets (not included)
Certifications CE; ETL listed: conforms to UL STD 61010-1, EN STD 61010-1; CSA C22.2 STD NO. 1010-1; RoHS compliant