Tate Raised Floor Systems (PDF) Increase Productivity with Longer Access to Hot Aisle Containment Systems OSHA exposure limits for working environments indicate a certain ratio of rest and work when working in high temperatures. These regulations may suggest periods of rest that limit the amount of time a person can work. Further to the limitations provided by OSHA it is important to create a comfortable working environment as some individuals may have a lower tolerance to heat. Airflow Performance Information (Paired with DirectAire) CFM @ Static Pressure (in. wc) | Hanger Install | Corner Lock Install | Closed | 100% Open | Closed | 100% Open | .02 | 51 | 945 | 164 | 1077 | .03 | 63 | 1146 | 204 | 1312 | .04 | 73 | 1313 | 239 | 1509 | .05 | 83 | 1460 | 271 | 1682 | .06 | 91 | 1592 | 299 | 1838 | .08 | 106 | 1824 | 349 | 2114 | .10 | 119 | 2026 | 394 | 2355 | .12 | 131 | 2208 | 435 | 2573 | .14 | 141 | 2373 | 472 | 2771 | .16 | 152 | 2527 | 508 | 2956 | .18 | 162 | 2672 | 542 | 3130 | .20 | 171 | 2807 | 573 | 3293 |
*Cooling capacities were calculated using the following formula:(CFM x Capture Index %) / 126(CFM needed to cool 1kW @ 25ºF ?T)= kW per rack. INCLUDED COMPONENTS - 4 X Tool less Roll Form Stringer Hangers
- 4 X Alternative Corner Lock Hangers
- 4 X Corner Sealing Shrouds Installed
REQUIRED COMPONENTS - DirectAire , or DirectAire X2
- 4 Or 16 Unit AC Power Supply
- SmartAire Power Cable (Green)
- Normally-Open Switch & Cable (By Other)
- SmartAire C (For Multiple Units in an Aisle)(Use Part # XXXXX)
- Power/Control Cable (Blue) (1 Per Ea. SmartAire C Unit(S))
UNDERSTRUCTURE OPTIONS - 24" Bolted Steel System
- 24" Wood Core Systems
- 60CM Bolted Steel System
|