| Mechanical |
|
| Height |
3.4 in. (8.6 cm.) |
| Width |
17.2 in. (43.7 cm.) |
| Depth |
23.6 in. (59.9 cm.) |
| Weight |
65 lbs. (29 kg.) |
| Environmental |
|
| Heat Dissipation (BTU) |
Line: 1257, Bat: 1755 |
| Audible Noise |
<50 dB |
| Operating Temperature |
-20˚C (-4˚F) to +40˚C (104˚F) with
batteries and -25˚C (-13˚F) to +55˚C (131 ˚F) without batteries |
| Storage Temperature |
-20°C (-4°F) to +40°C (104°F) with
batteries and -25°C (-13°F) to +55°C (131 °F) without batteries |
| Relative Humidity |
5–90% non-condensing |
| Electrical Input |
|
| Connection |
L5-30P |
| Input Cord |
6 ft. (1.8 m) |
| Input Voltage Range |
90-138 Vac |
| Nominal Voltage |
120V |
| Frequency |
50/60 Hz |
| Frequency Range |
45–65 Hz |
| Nominal Current |
25 A |
| Breaker Ratings |
30A |
| Generator Compatability |
Yes |
| Electrical Output |
|
| Output Receptacles |
(6) 5-20R, (1) L5-30R |
| On Utility Voltage Regulation |
±3% of nominal |
| On Battery Voltage Regulation |
±3% of nominal |
| Voltage Wave Shape (On Battery) |
Sine wave |
| Power Factor |
0.9 |
| Frequency Regulation |
±3% Hz online |
| Load Crest Factor |
3 to 1 |
| Battery |
|
| Maximum Number of Battery Packs |
4 |
| Battery Type |
72 Vdc; (6) 12V, 9 Ah |
| Half Load Runtime (in mins) |
13 |
| Full Load Runtime (in mins) |
5 |
| Battery Replacement |
Hot-swappable internal
and external batteries |
| Start On Battery |
Allows start of UPS
without utility input |
| Recharge Time |
Internal batteries: 3
hours. 1 EBM: 9 hours; 2 EBM: 15 hours; 3 EBM: 21 hours; 4 EBM: 27 hours |
| Communications |
|
| User Interface |
Graphical LCD with blue
backlight and text in English, French, German, Russian and Spanish |
| LEDs |
Four status-indicating
LEDs |
| Communication Ports |
(1) USB, (1) RS-232
serial, Relay output (common alarm standard) |
| Communications Slot |
Optional communication
slots (BD Slot) |
| Optional Communication Cards |
SNMP/Web card for
direct control and monitoring in SNMP-based networks, monitoring of UPS
status and meters through Web browser interface Relay card for
integration to industrial environment and building management systems,
remote shutdown for IBM AS/400 systems |
| Power Management Software |
Bundled software suite
CD |
| General |
|
| Topology |
Online,
double-conversion |
| Configuration |
Rackmount |
| Color |
Black |
| Rating (VA/Watts) |
3000/2700 |
| Diagnostics |
Full system self-test |
| Efficiency |
>95% in high-efficiency
mode; >86% in online mode |
| UPS Bypass |
Automatic bypass |
| Rail Kit Included |
Included with all
rackmount units |
| Warranty |
Two-year factory
warranty |
| Remote Emergency Power off (REPO) |
Emergency shutdown
control through the REPO port |
| Standards |
|
| Safety markings |
UL, cUL, VCCI |
| EMC Markings |
FCC Class A, EN55022 Class A |
| RoHS Compliance |
Yes |