For replacement product information call 1-866-722-5776.
| Mechanical |
|
| Height |
5.1 in. (13.0 cm.) |
| Width |
17.4 in. (44.2 cm.) |
| Depth |
19.1 in. (48.5 cm.) |
| Weight |
75.6 lbs. (34.3 kg.) |
| Environmental |
|
| Heat Dissipation (BTU) |
Line: 588, Bat: 3,071 |
| Audible Noise |
Max 45 dBA |
| Operating Temperature |
0˚C (32˚F) to +35°C (95˚F) |
| Storage Temperature |
-15˚C (5˚F) to +50˚C (122˚F) |
| Relative Humidity |
20–95% non-condensing |
| Altitude |
Up to 10,000 ft (3000M) without de-rating |
| Electrical Input |
|
| Connection |
L5-30P |
| Input Cord |
6 ft. (1.8 m) |
| Input Voltage Range |
80-151V (* The high and
low thresholds can be user adjusted using the downloadable UPS
Configuration tool) |
| Nominal Voltage |
120 VAC |
| Frequency |
50/60 Hz (auto-sensing) |
| Frequency Range |
47–70 Hz for 50 Hz
operation 56.5–70 Hz for 60 Hz operation |
| Nominal Current |
25.4 A |
| Breaker Ratings |
30A |
| Electrical Output |
|
| Output Receptacles |
(6) 5-20R, (1) L5-30R |
| On Utility Voltage Regulation |
102-132 Vac |
| On Battery Voltage Regulation |
-10%, +6% of nominal |
| Voltage Wave Shape (On Battery) |
Sine wave |
| Power Factor |
0.9 |
| Efficiency (on Battery) |
0.75 |
| Frequency Regulation |
0.1 Hz |
| Transfer Time |
1 to 4 ms, typical |
| Load Crest Factor |
3:1 |
| Load Segments |
Two individually
controlled output receptacles |
| Battery |
|
| Maximum Number of Battery Packs |
4 |
| Battery Type |
12V/9 Ah; sealed,
lead-acid; maintenance free |
| Half Load Runtime (in mins) |
10 |
| Full Load Runtime (in mins) |
3 |
| Battery Replacement |
Hot-swappable internal
batteries |
| Battery Voltage |
12V |
| Start On Battery |
Allows start of UPS
without utility input |
| Communications |
|
| LEDs |
13 status-indicating
LEDs |
| Communication Ports |
Serial Port RS-232
(RJ45) ports; USB Port As standard (HID). RS-232 and USB 6-ft
communication cables included |
| Optional Communication Cards |
ConnectUPS-MS network
management card and ModBus |
| Power Management Software |
Eaton Software Suite
CD-ROM (bundled with UPS) |
| General |
|
| Topology |
Line interactive |
| Color |
Black |
| Rating (VA/Watts) |
2880/2700 |
| Diagnostics |
Full system self-test
at power up |
| Efficiency |
>94% |
| Rail Kit Included |
Towers stands and
4-post rail kit included with all units |
| Warranty |
Three-year factory
warranty with online product registration |
| Remote Emergency Power off (REPO) |
Rear deck emergency
stop connector (for remote on/off and power off) |
| Standards |
|
| Safety markings |
UL 1778; UL497A; cUL (CAN/CSA C22.2, No.
107.1) |
| EMC Markings |
FCC Part 15 subpart B Class A |
| Markings |
UL; cUL |