Mechanical |
|
|
Dimensions (HxWxD) |
3.5 x 17.0 x 19.4 in. (89 x 432 x 494 mm.) |
|
Weight |
61 lbs. (27.67 kg.) |
|
Electrical Input |
|
|
Power Rating |
1440VA / 1340W |
|
Nominal Voltage |
120, 208 and 230 Vac |
|
Input Voltage Ranges (for user-selectable voltages) |
Low voltage: 77-152 V; High voltage: 154-288 V |
|
Operating Frequency |
50/60 Hz, Auto-sensing |
|
Frequency Range |
46-54 hz for 50 hz; 56-64 hz for 60 hz |
|
Connections |
|
|
Input Connections |
5-15P, 6 ft line cord |
|
Output Receptacles |
(6) 5-15R |
|
Battery |
|
|
Battery Type |
Sealed, lead-acid; maintenance free |
|
Battery Replacement |
Hot-swappable internal batteries and external batteries modules |
|
Recharge Time |
<3 hours to 90% usable capacity |
|
Start-On-Battery |
Allows start of UPS without utility input |
|
Electrical Output |
|
|
On Utility Voltage Regulation |
-10% to +6% of nominal |
|
On Battery Voltage Regulation |
±5%
RMS |
|
Voltage Wave Shape (on battery) |
Sine Wave |
|
Output Protection |
Short circuit protection |
|
Communications |
|
|
User Interface |
Front Control Panel |
|
Audible Alarms |
For various UPS alarm conditions, including: On Battery, Low Battery, Overload,
UPS fault |
|
Network Transient Protector |
UL 497 A, in/out jacks RJ45 (high voltage models network protection) & RJ11
(low voltage models modem protection) |
|
Communication Ports |
see Communications Slot |
|
Communication Slot |
RS-232 single serial module (standard) options available, see options chart |
|
Cable |
6-foot communications cable included |
|
Power Management Software |
Powerware Software Suite CD-ROM (bundled with UPS) |
|
General |
|
|
Electrical Power Module Replcmnt |
No |
|
Diagnostics |
Full system self-test on power up |
|
UPS Bypass |
No Bypass |
|
Transfer Time |
4ms typical, 6ms max |
|
Overload (normal operation) |
110% overload, shutdown after 3 minutes.
150% overload, shut down 10 cycles |
|
Environmental |
|
|
Operating Temperature |
0 to 40º C (32 to 104º F) |
|
Storage Temperature |
-15 to 50º C (5 to 122º F) |
|
Relative Humidity |
0% to 95% non-condensing |
|
Lightning & Surge Protection |
ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5 |
|
Surge Energy Rating |
high-energy 6500 A peak |
|
Audible Noise |
less than 40 dBA typical |
| Altitude
|
3000m (10,000 ft) without derating |