Electrical Input |
|
|
Voltage |
120 Vac Nominal |
| On
Line Voltage Range |
+20% for nominal voltage at full load |
|
Nominal Input Frequency |
45-65 Hz, 50/60 Hz; auto-sensing |
|
Input Protection |
Reset-able circuit breaker |
|
Connection |
6 ft. cord w/5-I5P |
|
Electrical Output |
|
|
Power Levels |
750VA / 500W |
| Online
Regulation |
-10%,
+6% of nominal voltageNominal -10% to +8% |
| On
Battery Frequency Regulation |
+/-0.1
Hz of nominal frequency |
|
Voltage Wave Shape |
Sine wave (during normal and battery operation) |
|
Indicators and Controls |
|
|
Front Panel LEDs |
Power
on, on battery, overload, and battery fault |
|
Front Panel Buttons |
On/Off
and alarm silence/self-test |
|
Communications Port |
DB9
female (UPS ships with communications cable); USB Interface Adapter is optional |
| Power
Factor |
0.67 |
|
Battery |
|
|
Battery Type |
Sealed,
maintenance-free lead-acid; starved electrolyte |
|
Battery Description |
(2) 12 V, 7.2 Ah |
| Battery
Recharge |
<
3 hours to 90% capacity |
| Battery
Runtime |
5
minutes minimum; See Battery Runtimes table |
| Start-On-Battery |
Startup
with UPS batteries in absence of utility power |
|
General |
|
| Topology |
Line-interactive |
| Network
Transient Protector |
In
and out RJ11 jack for telephone/modem protection (120 V models only) or
RJ45 for 10Base-T network cable; UL497A tested |
|
Environmental and safety |
|
|
Operating Temperature |
0oC to 40oC (32oF to 104oF)
UL tested at 25oC (77oF) |
| Safety
Markings |
UL,
cUL, and CSA; 230V models also CE and TUV |
| Safety
Conformance |
UL
1778, CAN/CSA C22.2, No. 107.1; 230 V models also EN 50091-1-1 and IEC 60950 |
|
EMC Markings |
FCC Class B |
|
Surge Suppression |
ANSI C62.41 Category A (formerly IEEE 587) |
|
Immunity |
IEC
801-2, -3, -4 |
|
Transit/Storage Temp. |
-15oC to 55oC (5oF to 131oF) |
|
Audible Noise |
< 45 dBA typical |
|
Relative Humidity |
5-95% non-condensing |