Electrical Input |
|
|
Nominal Voltage |
120 V Models are 110 V or 120 V user-selectable; 230 V models are 220 V,
230 V or 240 V user-selectable |
| Input
voltage ranges for user-selectable voltages |
+20% for nominal voltage at full load |
|
Operating Frequency |
50/60 Hz, Auto-sensing |
|
Frequency Range |
46-65 Hz |
|
Electrical Output |
|
|
On Utility Voltage Regulation |
-10%
to +6% of nominal |
| On
Battery voltage Regulation |
±5% RMS |
|
Voltage Wave Shape (on battery) |
Sine Wave |
|
Over Current Protection |
Electronic current limit |
|
Communications |
|
|
User Interface |
LED status display with AC power on, load Group, Overload, On Battery and
General Alarm indicators, Site Wiring Fault Indicator on rear panel for
low volt models. |
|
Audible Alarms |
For various UPS alarm conditions, including: On Battery, Low Battery, Overload,
UPS fault |
|
Network transient Protector |
UL 497 A, In/out jacks RJ45 (high voltage models network protection) & RJ11
(low voltage models modem protection) |
|
X-Slot Optional Communication cards |
ConnectUPS-X Web/SNMP/xHub Card; USB card ; Relay card |
|
Standard Communications |
1 x RS-232 Serial Port & 1 x xUSB Port |
|
Cable |
6-foot communications cable included |
|
Power Management Software |
Powerware Software Suite CD-ROM (bundled with UPS) |
|
Battery |
|
|
Battery Type |
Sealed, lead-acid; maintenance free |
|
Battery Replacement |
Hot-swappable internal batteries |
| Battery
Recharge |
<
3 hours to 90% capacity |
| Start-On-Battery |
Allows UPS operation without utility input |
|
General |
|
|
Diagnostics |
Self-test @ power up |
|
Transfer Time |
2-4ms typical |
|
Overload (normal operation) |
110% overload, shutdown after 3 minutes; 150% overload, shut down 10 cycles |
|
Environmental |
|
|
Operating Temperature |
0 to 40° C (32 to 104° F) |
| Safety
Markings |
120 V Models: UL; cUL
230 V Models: C-Tick; CE, TUV, cUL, UL |
| Safety
Conformance |
120 V Models: UL 1778; UL497A; cUL (CAN/CSA C22.2, No. 107.1)
230 V Models: UL1778, UL 497A (data line only);
cUL (CAN/CSA C22.2, No. 107.1); EN 50091-1-1 and IEC 60950 |
| EMC
Markings |
120 V Models: FCC Part 15 subpart J Class A, ICES-003; 230 V Models: EN
50091-2. FCC Part 15 subpart J Class A, ICES-003 |
| Surge
Suppression |
ANSI C62.41 Category A (formerly IEEE 587) |
| Audible
Noise |
<
40 dBA typical |
|
Altitude |
Up to 3000M (10,000 ft) without derating |