Upsite Technologies KoldLok 10012 Extended Raised Floor Grommet

Upsite Technologies KoldLok 10012 Extended Raised Floor Grommets are designed to seal a variety of existing perimeter openings, with the added flexibility of modification for large and unique openings.  Based on measurements at multiple data centers, 50-80% of valuable conditioned air is not reaching the air intake of IT equipment due to unsealed floor openings. This lost air, known as bypass airflow, contributes to IT equipment hotspots, cooling unit inefficiencies, and increasing infrastructure costs. KoldLok products specifically address bypass airflow and its detrimental effects on data center cooling.

Note: The Raised Floor Grommets are sold in a pack of 10.

Upsite Technologies KoldLok 10012 Extended Raised Floor Grommet - Click to enlarge



Price
$895.00
Sale Price
$877.00
Savings!
$18.00
Free Project Eval

Benefits of KoldLok Grommets

  • Increases existing cooling unit capacity
  • Reduces the need to purchase additional cooling units
  • Improves equipment reliability and extends equipment life
  • Increases static pressure under the raised floor and improves cool air delivery through perforated tiles and floor grates
  • Facilitates Cold Aisle/Hot Aisle best practices

KoldLok Features:

  • Compatible with both 24 inch and 600 mm tiles
  • Can be modified to seal unique cable openings
  • Integrate with the raised floor static dissipation system, providing 1 GigaOhm of resistance
  • Contain no loose or partially fastened parts, which can become separated or fall through the raised floor
  • 100% bypass airflow sealing in areas undisturbed by cable penetrations at static pressures up to 0.10 inches of water column
  • 100% bypass airflow sealing with four 1/2 inch cables penetrating the Grommet at the static pressure required to cool up to 3 kW/cabinet
  • 95% bypass airflow sealing with four 1/2 inch cables penetrating the Grommet at a static pressure of 0.50 inches of water column

 


KoldLok Extended Raised Floor Grommet Diagram
KoldLok Extended Raised Floor Grommet Diagram

KoldLok 10012 Specifications:

  • Maximum Cutout Size Sealed: 24 x 4 in. (610 x 102 mm.)
  • Usable Cable Area: 22 x 2.5 in. (559 x 64 mm.)
  • Height above the raised floor: 1 in. (25 mm.) with mounting system installed
  • 0.010 inch diameter upper filaments
  • 0.020 inch diameter lower filaments
  • Approximately 34,000 filaments
  • Premium-grade nylon Type 6, ensuring flexibility and self-sealing recovery
  • Floor Mounting System: Standard self-tapping screws or custom adhesive mounting kit
    consisting of:
    • Double-sided, pressure sensitive foam with adhesive backing
    • Polyethylene foam pads for static dissipation
    • All foam components are non-particulating
  • Filament holder: anodized aluminum alloy, black finish
  • End Caps: PC/ABS, black